Example 2
ANSI07000198.vsd
SMAI1:13
BLOCK
DFTSPFC
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:1
BLOCK
DFTSPFC
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:25
BLOCK
DFTSPFC
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI07000199 V1 EN-US
Figure 431:
Configuration for using an instance in task time group 2 as DFT
reference.
Assume instance SMAI4:16 in task time group 2 has been selected in the configuration
to control the frequency tracking for all instances. Observe that the selected reference
instance (i.e. frequency tracking master) must be a voltage type. Observe that positive
sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
for numbering):
SMAI1:1 – SMAI12:12:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input as
reference (SMAI4:16)
For task time group 2 this gives the following settings:
SMAI1:13:
DFTRefExtOut
=
DFTRefGrp4
to route SMAI4:16 reference to the
SPFCOUT output,
DFTReference
=
DFTRefGrp4
for SMAI1:13 to use SMAI4:16 as
reference (see Figure
) SMAI2:14 – SMAI12:24:
DFTReference
=
DFTRefGrp4
to
use SMAI4:16 as reference.
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input as
reference (SMAI4:16)
1MRK 504 163-UUS A
Section 24
Basic IED functions
Transformer protection RET670 2.2 ANSI
975
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...