During a single-phase reclosing cycle, the autoreclosing device must block the
directional comparison ground-fault communication scheme.
The communication logic module enables blocking as well as permissive under/
overreaching schemes. The logic can also be supported by additional logic for weak-
end infeed and current reversal, included in the Current reversal and weak-end infeed
logic for residual overcurrent protection (ECRWPSCH, 85) function.
Metallic communication paths adversely affected by fault generated noise may not be
suitable for conventional permissive schemes that rely on signal transmitted during a
protected line fault. With power line carrier, for example, the communication signal
may be attenuated by the fault, especially when the fault is close to the line end,
thereby disabling the communication channel.
To overcome the lower dependability in permissive schemes, an unblocking function
can be used. Use this function at older, less reliable, power line carrier (PLC)
communication, where the signal has to be sent through the primary fault. The
unblocking function uses a guard signal CRG, which must always be present, even
when no CR signal is received. The absence of the CRG signal during the security time
is used as a CR signal. This also enables a permissive scheme to operate when the line
fault blocks the signal transmission. Set the
tSecurity
to 35 ms.
16.5.3
Setting guidelines
M13920-4 v7
The parameters for the scheme communication logic for residual overcurrent protection
function are set via the local HMI or PCM600.
The following settings can be done for the scheme communication logic for residual
overcurrent protection function:
Operation
:
Disabled
or
Enabled
.
SchemeType
: This parameter can be set to
Off
,
Intertrip
,
Permissive UR
,
Permissive
OR
or
Blocking
.
tCoord
: Delay time for trip from ECPSCH (85) function. For Permissive under/
overreaching schemes, this timer shall be set to at least 20 ms plus maximum reset time
of the communication channel as a security margin. For Blocking scheme, the setting
should be > maximum signal transmission time +10 ms.
Unblock
: Select
Off
if unblocking scheme with no alarm for loss of guard is used. Set
to
Restart
if unblocking scheme with alarm for loss of guard is used.
tSendMin
: Time duration, the carrier send signal is prolonged.
1MRK 504 163-UUS A
Section 16
Scheme communication
Transformer protection RET670 2.2 ANSI
833
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...