For a busbar grounding switch on bypass busbar C, these conditions are valid:
789OPTR (bay 1)
BB_DC_OP
VP_BB_DC
EXDU_BB
en04000510_ansi.vsd
AND
AND
AND
789OPTR (bay n)
. . .
. . .
. . .
VP789TR (bay 1)
VP789TR (bay n)
EXDU_BB (bay 1)
EXDU_BB (bay n)
. . .
. . .
. . .
. . .
. . .
. . .
ANSI04000510 V1 EN-US
Figure 357:
Signals from bypass busbar to busbar grounding switch
15.3.7.3
Signals in double-breaker arrangement
M15053-83 v4
The busbar grounding switch is only allowed to operate if all disconnectors of the bus
section are open.
en04000511_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
BB_ES
DB_BUS
(WA1)A1
(WA2)B1
B2
A2
DB_BUS
ANSI04000511 V1 EN-US
Figure 358:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
All disconnectors of this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar are valid.
EXDU_BB
No transmission error from any bay that contains the above information.
These signals from each double-breaker bay (DB_BUS) are needed:
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
749
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...