When single pole tripping is required, a detailed study of the voltages
during phase-to-phase and phase-to-ground faults should be done, at
different fault locations.
16.4
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH (85)
SEMOD155635-1 v2
16.4.1
Identification
SEMOD156467-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for phase segregated
communication
ZC1WPSCH
-
85
16.4.2
Application
SEMOD156558-1 v1
SEMOD156537-5 v4
Current reversal logic
If parallel lines are connected to common buses at both terminals, overreaching
permissive communication schemes can trip unselectable due to current reversal. The
unwanted tripping affects the healthy line when a fault is cleared on the other line. This
lack of security results in a total loss of interconnection between the two buses.
To avoid this kind of disturbances, fault current reversal logic (transient blocking logic)
can be used.
The unwanted operations that might occur can be explained by looking into
. Assume that the fault has been taken place close to breaker B1. At
first, the protection A2 at A side will detect a fault in forward direction and send a
communication signal to the protection B2 at remote end, which is measuring a fault in
reverse direction.
1MRK 504 163-UUS A
Section 16
Scheme communication
Transformer protection RET670 2.2 ANSI
829
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...