Remedy:
- carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the original
cables should be used (ensure compliance with the maximum cable length).
F36950
Hub: Internal software error
Message value:
%1
Drive object:
All objects
Reaction:
OFF2 (NONE)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if required, upgrade the firmware in the DRIVE-CLiQ Hub Module to a more recent version.
- contact Technical Support.
F37001
HF Damping Module: overcurrent
Message value:
Fault cause: %1 bin
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an overcurrent condition.
- HF Choke Module or HF Damping Module defective.
- Resonance frequency of the output filter was excited.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Remedy:
- check HF Choke Module and HF Damping Module and if required, replace.
- reduce the motor power in the proximity of the fault-generating frequency.
Note:
HF Choke Module (reactor module)
HF Damping Module
F37002
HF Damping Module: Damping voltage too high
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The damping voltage has reached an inadmissibly high value.
- a motor harmonic with a high amplitude has coincided with the resonance frequency of the output filter.
- the current controller excessively excites the resonance of the output filter.
Fault value (r0949, interpret decimal):
Damping voltage in the case of a fault [mV].
Remedy:
- reduce the motor power in the proximity of the fault-generating frequency.
- check the current controller and if required, adapt.
- if required, use another motor.
Note:
HF Damping Module
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
708
Operating Instructions, 12/2017, A5E41702836B AA