![Siemens SIMOTICS S-1FK2 Operating Instructions Manual Download Page 428](http://html.mh-extra.com/html/siemens/simotics-s-1fk2/simotics-s-1fk2_operating-instructions-manual_379045428.webp)
Remedy:
- check the motor load and if required, reduce.
- check the motor ambient temperature.
- check activation of the motor temperature model (p0612).
Motor temperature model 1 (I2t):
- check the thermal time constant (p0611).
- check alarm threshold.
Motor temperature model 3:
- check the motor type.
- check alarm threshold.
- check the model parameters.
See also: r0034
Reaction upon N: NONE
Acknowl. upon N: NONE
F07013
Drive: Motor temperature model configuration fault
Message value:
%1
Drive object:
All objects
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred in the configuration of the motor temperature model.
Fault value (r0949, interpret decimal):
300:
Motor temperature model 3: The sensor does not supply the necessary sensor temperature for the thermal model.
301:
Motor temperature model 3: The sensor type is unknown.
302:
Motor temperature model 3: At least one other temperature model was simultaneously activated.
303:
Motor temperature model unknown in the actual firmware version.
Remedy:
- check the encoder type.
- check the motor type.
- check activation of the motor temperature model (p0612).
- check the parameters of the motor temperature model (p5350 and following).
A07014 (N)
Drive: Motor temperature model configuration alarm
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A fault has occurred in the configuration of the motor temperature model.
Alarm value (r2124, interpret decimal):
1:
All motor temperature models: It is not possible to save the model temperature
300:
Motor temperature model 3: Threshold value for alarm (r5398) is higher than the threshold value for fault (r5399).
Remedy:
- set the response for motor overtemperature to "Alarm and fault, no reduction of I_max" (p0610 = 2).
- check and correct the threshold values (r5398, r5399).
Reaction upon N: NONE
Acknowl. upon N: NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
426