Power unit: 24 V power supply overloaded by PM
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply through the Power Module (PM) is overloaded.
An external 24 V power supply via X124 on the Control Unit is not connected.
Remedy:
Connect an external 24 V power supply via X124 at the Control Unit.
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY (POWER ON)
A30502
Power unit: DC link overvoltage
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The power unit has detected overvoltage in the DC link on a pulse inhibit.
- device connection voltage too high.
- line reactor incorrectly dimensioned.
Alarm value (r0949, interpret decimal):
DC link voltage [1 bit = 100 mV].
See also: r0070
Remedy:
- check the device supply voltage (p0210).
- check the dimensioning of the line reactor.
See also: p0210
F30600
SI P2: STOP A initiated
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function in monitoring channel 2 has detected a fault and initiated a STOP A (STO
via the safety switch-off signal path of monitoring channel 2).
- forced checking procedure (test stop) of the safety switch-off signal path of monitoring channel 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, decimal interpretation):
0: Stop request from the Control Unit.
1005: STO active although STO not selected and there is no internal STOP A present.
1010: STO inactive although STO is selected or an internal STOP A is present.
1011: internal error for STO deselected in monitoring channel 2.
9999: Subsequent response to fault F30611.
Remedy:
- select Safe Torque Off and de-select again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- replace drive.
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
CU: Control Unit
SI: Safety Integrated
STO: Safe Torque Off
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
517