Remedy:
- check parameterization in the parameters involved and correct if required.
- ensure equality by copying the SI data to the second channel and then carry out an acceptance test.
- check monitoring clock cycle for equality (p9500, p9300).
This message can be acknowledged without a POWER ON as follows (safe acknowledgment):
- onboard F-DI (only CU310-2).
- PROFIsafe.
- machine control panel.
C30714
SI Motion P2: Safely Limited Speed exceeded
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive had moved faster than that specified by the velocity limit value. The drive is stopped as a result of the configured
stop response.
Message value (r2124, interpret decimal):
100: SLS1 exceeded.
200: SLS2 exceeded.
300: SLS3 exceeded.
400: SLS4 exceeded.
1000: Encoder limit frequency exceeded.
Remedy:
- check the traversing/motion program in the control.
- check the limits for the "SLS" function and if required adapt.
This message can be acknowledged without a POWER ON as follows (safe acknowledgment):
- PROFIsafe.
- machine control panel.
Note:
SI: Safety Integrated
SLS: Safely Limited Speed
C30715
SI Motion P2: Safely Limited Position exceeded
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The axis has moved past a parameterized position that is monitored by the "SLP" function.
Message value (r9749, interpret decimal):
10: SLP1 violated.
20: SLP2 violated.
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
538
Operating Instructions, 12/2017, A5E41702836B AA