![Siemens SIMOTICS S-1FK2 Operating Instructions Manual Download Page 497](http://html.mh-extra.com/html/siemens/simotics-s-1fk2/simotics-s-1fk2_operating-instructions-manual_379045497.webp)
F30005
Power unit: Overload I2t
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit was overloaded (r0036 = 100 %).
- the permissible rated power unit current was exceeded for an inadmissibly long time.
- the permissible load duty cycle was not maintained.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the motor and power unit rated currents.
See also: p0307, r0307
F30006
Power unit: Thyristor Control Board
Message value:
-
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The Thyristor Control Board (TCB) of the Basic Line Module signals a fault.
- there is no line supply voltage.
- the line contactor is not closed.
- the line supply voltage is too low.
- line supply frequency outside the permissible range (45 ... 66 Hz).
- there is a DC link short-circuit.
- there is a DC link short-circuit (during the precharging phase).
- the motor either has a short-circuit or insulation fault (from an inverter connected to the DC link).
- voltage supply for the Thyristor Control Board outside the nominal range (5 ... 18 V) and line voltage >30 V.
- there is an internal fault in the Thyristor Control Board.
Remedy:
The faults must be saved in the Thyristor Control Board and must be acknowledged. To do this, the supply voltage of the
Thyristor Control Board must be switched out for at least 10 s!
- check the line supply voltage
- check or energize the line contactor.
- check the monitoring time and, if required, increase (p0857).
- if required, observe additional power unit messages/signals.
- check the DC link regarding short-circuit or ground fault.
- check the motor regarding short-circuit or ground fault.
- evaluate diagnostic LEDs for the Thyristor Control Board.
F30008
Power unit: Sign-of-life error cyclic data
Message value:
-
Drive object:
All objects
Reaction:
Servo: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The Control Unit has not punctually updated the cyclic setpoint telegram to the power unit. The number of consecutive
tolerated sign of life errors has exceeded the fault threshold (p7789) set in the power unit.
Remedy:
- for projects with the VECTOR drive object, check whether p0117 = 6 has been set on the Control Unit.
- increase the fault threshold (p7789).
- check the Motor Module, and if required replace.
Faults and alarms