Cause:
The forced checking procedure (test stop) for the safe motion monitoring functions is already selected when booting, which
is not permissible.
This is the reason that the test is only carried out again after first selecting the forced checking procedure.
Note:
This message does not result in a safety stop response.
Remedy:
De-select the forced checking procedure for the safe motion monitoring functions and then select again.
Note:
The signal source to select the forced checking procedure is set via binector input p9705.
SI: Safety Integrated
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY (POWER ON)
A01697 (F)
SI Motion: Test stop for motion monitoring functions required
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time set in p9559 for the forced checking procedure (test stop) for the safe motion monitoring functions has been
exceeded. A new forced checking procedure is required.
After the next time the forced checking procedure is selected, the message is withdrawn and the monitoring time is reset.
Note:
- this message does not result in a safety stop response.
- As the switch-off signal paths are not automatically checked during booting, an alarm is always issued once booting is
complete.
- the test must be performed within a defined, maximum time interval (p9559, maximum of 9000 hours) in order to comply
with the requirements as laid down in the standards for timely fault detection and the conditions to calculate the failure
rates of safety functions (PFH value). Operation beyond this maximum time period is permissible if it can be ensured that
the forced checking procedure is performed before persons enter the hazardous area and who are depending on the safety
functions correctly functioning.
See also: p9559, r9765
Remedy:
Carry out the forced checking procedure of the safety motion monitoring functions.
The signal source to select the forced checking procedure is set via binector input p9705.
Note:
SI: Safety Integrated
Reaction upon F: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY (POWER ON)
A01698 (F)
SI P1 (CU): Commissioning mode active
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The commissioning of the "Safety Integrated" function is selected.
This message is withdrawn after the safety functions have been commissioned.
Note:
- this message does not result in a safety stop response.
- in the safety commissioning mode, the "STO" function is internally selected.
See also: p0010
Remedy:
Not necessary.
Note:
CU: Control Unit
SI: Safety Integrated
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
375
Summary of Contents for SIMOTICS S-1FK2
Page 2: ......
Page 766: ...Index SINAMICS S210 servo drive system 764 Operating Instructions 12 2017 A5E41702836B AA ...
Page 767: ......