6.10.2
Restoring externally backed-up parameter settings
If you load the externally backed-up parameter settings to the converter again, you restore the
converter state to the time of the data backup. You can also use the externally backed-up files
for a series commissioning.
1. Click "Browse" in the "Restore Parameters From File" setting area.
2. Select the data backup file in your file system.
The data backup file is now displayed in the view.
3. Click "Restore" in the "Restore Parameters From File" setting area.
The data backup is loaded. The converter is then restarted. You must log in to the Web
server again.
4. Log in to the Web server again.
6.10.3
Restoring the factory settings
If required, you can restore the factory settings for your converter.
1. In view "Backup and restore", click on "Restore Factory Settings".
2. Confirm the prompt with "Restore Factory Settings".
The restoration of the factory settings starts. The converter is then restarted. You must log
in to the Web server again.
3. Reassign the administrator password and log on to the Web server with it.
Commissioning and diagnostics in the Web server
6.10 Backup and restore
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA