Reaction:
NONE
Acknowledge:
NONE
Cause:
Encoderless operation is active due to a fault (r1407.13 = 1).
Note:
The behavior for faults has been set to ENCODER fault response in p0491.
Remedy:
- remove the cause of a possible encoder fault.
- carry out a POWER ON (switch-off/switch-on) for all components.
A07580 (F, N) Drive: No Sensor Module with matching component number
Message value:
Encoder data set: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Sensor Module with the component number specified in p0141 was not found.
Alarm value (r2124, interpret decimal):
Encoder data set involved (index of p0141).
Remedy:
Correct parameter p0141.
Reaction upon F: Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
F07754
Drive: Incorrect shutoff valve configuration
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An incorrect shutoff valve configuration was detected.
Fault value (r0949, interpret decimal):
100:
Enable Safety Integrated (p9601/p9801), but p0218.0 = 0 (shutoff valve not available).
101:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when switching
on the shutoff valve (p0230 < p9625[0]/p9825[0]).
102:
The manipulated variable inhibit time is set less than the wait time to evaluate the feedback signal contacts when switching
off the shutoff valve (p0230 < p9625[1]/p9825[1]).
Remedy:
For fault value = 100:
Check the enable of Safety Integrated and the shutoff valve (p9601/p9801, p0218.0).
For fault value = 101:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when switching
on the shutoff valve (p0230 > p9625[0]/p9825[0]).
For fault value = 102:
Set the manipulated variable inhibit time higher than the wait time to evaluate the feedback signal contacts when switching
off the shutoff valve (p0230 > p9625[1]/p9825[1]).
F07800
Drive: No power unit present
Message value:
-
Drive object:
All objects
Reaction:
NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
460
Operating Instructions, 12/2017, A5E41702836B AA