Cause:
An error has occurred when downloading PSxxxyyy.ACX or PTxxxyyy.ACX files from the non-volatile memory.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2:
255: Incorrect drive object type.
254: Topology comparison unsuccessful -> drive object type was not able to be identified.
Reasons could be:
- incorrect component type in the actual topology
- Component does not exist in the actual topology.
- Component not active.
Additional values:
Only for internal Siemens troubleshooting.
Byte 4, 3:
Only for internal Siemens troubleshooting.
Remedy:
- if you have saved the project data using the commissioning tool, download the project again. Save using the function
"Copy RAM to ROM" or with p0977 = 1. This means that the parameter files are again completely written to the non-volatile
memory.
- replace the memory card or Control Unit.
For byte 2 = 255:
- correct the drive object type (see p0107).
Reaction upon A: NONE
Acknowl. upon A: NONE
F01039 (A)
ACX: Writing to the parameter back-up file was unsuccessful
Message value:
%1
Drive object:
All objects
Reaction:
Servo: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
Writing to at least one parameter back-up file PSxxxyyy.*** in the non-volatile memory was unsuccessful.
- in the directory /USER/SINAMICS/DATA/ at least one parameter back-up file PSxxxyyy.*** has the "read only" file attribute
and cannot be overwritten.
- there is not sufficient free memory space available.
- the non-volatile memory is defective and cannot be written to.
Fault value (r0949, interpret hexadecimal):
dcba hex
a = yyy in the file names PSxxxyyy.***
a = 000 --> consistency back-up file
a = 001 ... 062 --> drive object number
a = 070 --> FEPROM.BIN
a = 080 --> DEL4BOOT.TXT
a = 099 --> PROFIBUS parameter back-up file
b = xxx in the file names PSxxxyyy.***
b = 000 --> data save started with p0977 = 1 or p0971 = 1
b = 010 --> data save started with p0977 = 10
b = 011 --> data save started with p0977 = 11
b = 012 --> data save started with p0977 = 12
d, c:
Only for internal Siemens troubleshooting.
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
302
Operating Instructions, 12/2017, A5E41702836B AA