Cause:
The topology comparison has detected a motor with DRIVE-CLiQ in the actual topology that has been incorrectly inserted
with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01416
Topology: Component additionally inserted
Message value:
%1, to %2, %3, connection: %4
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has found a component in the actual topology which is not specified in the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = component class (% 2)
cc = connection number (%4)
bb = component class of the additional component (%1)
aa = component number (%3)
Note:
The component class of the additional component is contained in bb.
The component is described in dd, cc and aa, where the additional component is inserted.
Component class and connection number are described in F01375.
Remedy:
Adapting topologies:
- remove the additional component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01420
Topology: Component different
Message value:
Component: %1, target: %2, actual: %3, difference: %4
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
334
Operating Instructions, 12/2017, A5E41702836B AA