Cause:
The parameters of an individual drive object were saved (p0971 = 1), although there is still no backup of all drive system
parameters.
The saved object-specific parameters are not loaded the next time that the system powers up.
For the system to successfully power up, all of the parameters must have been completely backed up.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Save all parameters (p0977 = 1 or "copy RAM to ROM").
See also: p0977 (Save all parameters)
Reaction upon F: Servo: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F01033
Units changeover: Reference parameter value invalid
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing over the units to the referred representation type, it is not permissible for any of the required reference
parameters to be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
Remedy:
Set the value of the reference parameter to a number different than 0.0.
See also: p0304, r0304, p0305, r0305, p2000, p2003
F01034
Units changeover: Calculation parameter values after reference value change unsuccessful
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The change of a reference parameter meant that for an involved parameter the selected value was not able to be re-
calculated in the per unit representation. The change was rejected and the original parameter value restored.
Fault value (r0949, parameter):
Parameter whose value was not able to be re-calculated.
See also: p0304, r0304, p0305, r0305, p2000, p2003
Remedy:
- Select the value of the reference parameter such that the parameter involved can be calculated in the per unit
representation.
- Technology unit selection (p0595) before changing the reference parameter p0596, set p0595 = 1.
A01035 (F)
ACX: Parameter back-up file corrupted
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
300
Operating Instructions, 12/2017, A5E41702836B AA