09
Bandwidth bit 2 (LF)
Yes
No
-
10
Measuring periods bit 0
Yes
No
-
11
Measuring periods bit 1
Yes
No
-
12
Inject noise onto speed setpoint
Yes
No
-
13
Do not reduce Kp for measurement
Yes
No
-
14
Current setpoint filter that inverts the control loop
Yes
No
-
Dependency:
See also: r5293, p5296
Note
HF: High Frequency
LF: low frequency
For bit 00:
A PRBS signal (pseudo random binary signal) is superimposed on the current setpoint to be able to better identify the
mechanical controlled system.
For bit 01:
The identified mechanical resonance points are suppressed using current setpoint filters.
For bit 02:
The maximum speed controller gain is determined from the identified mechanical controlled system.
For bits 03, 04:
The measured value buffer length is set using these bits:
Bit 04 = 0 and bit 03 = 0 -> buffer length = 256
Bit 04 = 0 and bit 03 = 1 -> buffer length = 512
Bit 04 = 1 and bit 03 = 0 -> buffer length = 1024
Bit 04 = 1 and bit 03 = 1 -> buffer length = 2048
For bit 05:
A Hamming window is used to filter the measured time signals.
For bit 06:
The measurement checks the current controller frequency response and this is taken into account in the speed
controller loop. For high amplitudes in p5298, it is possible that the measurement is unsuccessful, as the converter
reaches its voltage limit.
For bits 07, 08, 09:
The measurement bandwidth is set using these bits:
Bit 09 = 0, bit 08 = 0, bit 07 = 0 -> bandwidth = 50 Hz
Bit 09 = 0, bit 08 = 0, bit 07 = 1 -> bandwidth = 100 Hz
Bit 09 = 0, bit 08 = 1, bit 07 = 0 -> bandwidth = 200 Hz
Bit 09 = 0, bit 08 = 1, bit 07 = 1 -> bandwidth = 400 Hz
Bit 09 = 1, bit 08 = 0, bit 07 = 0 -> bandwidth = 800 Hz
Bit 09 = 1, bit 08 = 0, bit 07 = 1 -> bandwidth = 1600 Hz
Zu Bit 10, 11:
Number of measuring periods.
Bit 11 = 0 and bit 10 = 0 -> number of measurements = 1
Bit 11 = 0 and bit 10 = 1 -> number of measurements = 2
Bit 11 = 1 and bit 10 = 0 -> number of measurements = 4
Bit 11 = 1 and bit 10 = 1 -> number of measurements = 8
For bit 12:
The PRBS signal is switched to the speed setpoint (in front of the filter).
For bit 13:
The input signal for the torque actual value is taken from in front of the current setpoints filters.
p5292
Controller optimization dynamic factor
Changeable: T, U
Data type: FloatingPoint32
P group: -
Min: 25.0 [%]
Max: 125.0 [%]
Def: 80.0 [%]
Description:
Sets the dynamic factor for optimizing the speed controller when One Button Tuning is activated (p5300 = 1).
Dependency:
The higher the value in p5292, the lower the value in r5274.
See also: p5291
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
257