Cause:
Safety parameters have been changed; these will only take effect following a warm restart or POWER ON (see alarm
A01693).
A partial power up (boot) with modified configuration was then performed.
Remedy:
- carry out a warm restart
- carry out a POWER ON (switch-off/switch-on).
F01680
SI Motion P1 (CU): Checksum error safety monitoring functions
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The actual checksum over the safety-relevant parameters, calculated and entered by the drive, does not match the
reference checksum last saved for the last machine acceptance.
Safety-relevant parameters have been changed or a fault is present.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, decimal interpretation):
0: Checksum error for SI parameters for motion monitoring.
1: Checksum error for SI parameters for actual values.
2: Checksum error for SI parameters for component assignment.
Remedy:
- check the safety-relevant parameters and if required, correct.
- execute the function "Copy RAM to ROM".
- perform a POWER ON if safety parameters requiring a POWER ON have been modified.
- carry out an acceptance test.
F01681
SI Motion P1 (CU): Incorrect parameter value
Message value:
Parameter: %1, supplementary information: %2
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
366