Note
In an extended sense, bus failure is interpreted here as a communication fault in the control signals of the safety
functions (e.g. via PROFIsafe).
SDI: Safe Direction (safe motion direction)
p9568
SI Motion SAM/SBR speed limit
Changeable: C2(95)
Data type: FloatingPoint32
P group: Safety Integrated
Min: 0.00 [mm/min]
Max: 1000.00 [mm/min]
Def: 0.00 [mm/min]
Description:
Sets the velocity limit for the "SAM" and "SBR" functions.
If the drive is being ramped down, but accelerates by the tolerance in p9548, then the SAM function identifies this and
a STOP A is initiated.
The monitoring operates as follows:
- monitoring by SAM is activated for SS1 (or STOP B) and SS2 (or STOP C).
- the SAM limit value is frozen after the velocity limit in p9568 is undershot.
- SAM monitoring is still executed until the transition time to SOS/STO has expired.
Note
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the speed monitoring)
For p9568 = 0, the following applies:
The value in p9546 (SSM) is applied as the velocity limit for SAM/SBR.
p9570
SI Motion acceptance test mode
Changeable: T, U
Data type: Integer16
P group: Safety Integrated
Min: 0000 hex
Max: 00AC hex
Def: 0000 hex
Description:
Setting to select and de-select the acceptance test mode.
Value:
0:
[00 hex] De-select the acceptance test mode
172:
[AC hex] Select the acceptance test mode
Dependency:
See also: p9558, r9571, p9601
See also: C01799
Note
Acceptance test mode can only be selected if the safe motion monitoring functions are enabled.
r9571
SI Motion acceptance test status
Data type: Integer16
P group: Safety Integrated
Description:
Displays the status of the acceptance test mode.
Value:
0:
[00 hex] Acc_mode inactive
12:
[0C hex] Acc_mode not possible due to POWER ON fault
13:
[0D hex] Acc_mode not possible due to incorrect ID in p9570
15:
[0F hex] Acc_mode not possible due to expired Acc_timer
172:
[AC hex] Acc_mode active
Dependency:
See also: p9558, p9570
See also: C01799
p9580
SI Motion stop response delay bus failure
Changeable: C2(95)
Data type: FloatingPoint32
P group: Safety Integrated
Min: 0.00 [ms]
Max: 800.00 [ms]
Def: 0.00 [ms]
Description:
Sets the delay time, after which the stop response parameterized in p9612 for bus failure is executed.
Dependency:
See also: p9563
Parameters
12.2 List of parameters
SINAMICS S210 servo drive system
272
Operating Instructions, 12/2017, A5E41702836B AA