F07515
Drive: Power unit and motor incorrectly connected
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A power unit (via PDS) was assigned to a motor (via MDS) in a drive data set that is not connected in the target topology.
It is possible that a motor has not been assigned to the power unit (p0131).
Fault value (r0949, interpret decimal):
Number of the incorrectly parameterized drive data set.
Remedy:
- assign the drive data set to a combination of motor and power unit permitted by the target topology.
- adapt the target topology.
- if required, for a missing motor, recreate the component (drive Wizard).
F07516
Drive: Re-commission the data set
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The assignment between the drive data set and motor data set (p0186) or between the drive data set and the encoder
data set was modified (p0187). This is the reason that the drive data set must re-commissioned.
Fault value (r0949, interpret decimal):
Drive data set to be re-commissioned.
Remedy:
Commission the drive data set specified in the fault value (r0949).
F07517
Drive: Encoder data set changeover incorrectly parameterized
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
In at least two drive data sets (DDS), the same motor data set (MDS) is assigned different encoder data sets (EDS) for
the motor encoder. In various DDSs, it is not permissible for an MDS to have different motor encoders.
The following parameterization therefore results results in an error:
DDS0: p0186[0] = 0, p0187[0] = 0
DDS1: p0186[1] = 0, p0187[1] = 1
Fault value (r0949, interpret decimal):
The lower 16 bits indicate the first DDS. The upper 16 bits indicate the second DDS.
Remedy:
Create two MDS with the same motor data in order to operate one motor with different motor encoders.
Example:
DDS0: p0186[0] = 0, p0187[0] = 0
DDS1: p0186[1] = 1, p0187[1] = 1
F07518
Drive: Motor data set changeover incorrectly parameterized
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY