A07998
Drive: Motor data identification active on another drive
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The motor data identification is activated on the drive object specified in the alarm value, and interlocks the other drive
objects so they cannot be switched on.
Alarm value (r2124, interpret decimal):
Drive object with the active motor data identification.
Remedy:
- wait for the complete execution of the motor data identification of the drive object designated in the alarm value.
- deselect the motor data identification for the drive object designated in the alarm value (p1910 = 0 or p1960 = 0).
A07999
Drive: Motor data identification cannot be activated
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Closed-loop control is enabled on a SERVO drive object type. To select motor data identification, pulses must be
suppressed for all SERVO drive objects.
Alarm value (r2124, interpret decimal):
Drive object with enabled closed-loop control.
Remedy:
Withdraw the pulse enable on all drives and re-activate the motor data identification.
F08000 (N, A) TB: +/-15 V power supply faulted
Message value:
%1
Drive object:
All objects
Reaction:
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Terminal Board 30 detects an incorrect internal power supply voltage.
Fault value (r0949, interpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy:
- replace Terminal Board 30.
- replace Control Unit.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F08010 (N, A) TB: Analog-digital converter
Message value:
-
Drive object:
All objects
Reaction:
Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The analog/digital converter on Terminal Board 30 has not supplied any converted data.
Remedy:
- check the power supply.
- replace Terminal Board 30.
Reaction upon N: NONE
Acknowl. upon N: NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
487