15-4
Protective function
Trip
Over Voltage, Under Voltage, Over Current, Over Current2, Ground Fault current
detection, Inverter Overheat, Motor Overheat, Output Phase Open, Overload
Protection, Communication Error, Loss of Speed Command, Hardware Fault, Fan trip,
Brake error
Alarm
Stall prevention, overload
Momentary
Power
Loss
Below 15 msec: Continuous operation (should be within rated input voltage, rated
output power).
Above 15 msec: Auto restart enable
Environment
Degree of
protection
IP20
Ambient temp
–10
°
C ~ 50
°
C
Storage temp
–20
°
C ~ 65
°
C
Humidity
Below 90% RH (no condensation)
Altitude/Vibration Below 1,000m, 5.9m/sec
2
(0.6G)
Atmospheric
pressure
70~106 kPa
Location
Protected from corrosive gas, combustible gas, oil mist or dust
15.1 Temperature Derating Information
Load and ambient temperature classified by the Carrier Frequency
CAUTION
1) The above graph is only applied when the inverter is operated in the allowable temperature. Pay
attention to the air cooling when the inverter is installed in a panel box, and the inside temperature
should be within an allowable temperature range.
2) This derating curve is based on inverter current rating when rated motor is connected.
% of Drive
Rated Amps
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
Carrier Frequency in kHz
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
72%
58%
40
℃
Rating
41
℃
~ 50
℃
Rating
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...