9-2
Frequency setting via –10 ~ +10[V] input
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive group 0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
2
0 ~ 8
0
I/O group
I1
[Filter time constant for negative
input V1]
10
0 ~ 9999
10
I2
[V1 input minimum negative
voltage]
-
0 ~ –10
0.0
V
I3
[Frequency corresponding to I2] -
0 ~ 400
0.00
Hz
I4
[V1 input max. negative voltage] -
0 ~ 10
10.00
V
I5
[Frequency corresponding to I4] -
0 ~ 400
50.00
Hz
I6 ~ I10 [V1 input positive]
Set
Frq
– [Frequency Mode] to 2.
The set frequency can be monitored in
0.00
- [Frequency Command].
Apply –10V ~ +10V signal between V1 and CM terminal.
Output frequency corresponding to –10V ~ +10V input voltage to V1 terminal
V1
CM
When using - 10 ~ 10V from external
circuit
- 10 ~ +10 V
Output freq
(Positive)
Output freq
(Negative)
Input
voltage
0~ 10[ V]
- 10~ 0[ V]