9-6
Frequency setting via RS 485 communication
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
0.0
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
7
0 ~ 8
0
Select 7 in Frq code of Drive group.
Related codes: I59, I60, I61
Refer to Chapter 13. RS485 communication.
Frequency setting via Digital Volume (up-down)
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
0.0
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
8
0 ~ 8
0
Select 8 in Frq code of Drive group.
Related codes: I17 ~ 24.
Among the multifunction inputs (P1 ~ P8), select two terminals to be used for up-down.
Refer to Chapter 7, I/O 2 Group.
Analog Hold
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
Frq
[Frequency Mode]
2 ~ 7
0 ~ 7
0
I/O group I17
[Multi-function input terminal
P1 define]
-
0 ~ 29
0
~
~
I24
[Multi-function input
terminal P8 define]
23
7
It is available when Frq code setting is 2 ~ 7.
Select one terminal to be used for Analog Hold command among Multi-function input
terminal (P1 ~ P8).
When P8 terminal is selected,
Frequency
P8
Run command
Set freq.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...