9-19
Manual torque boost
Group
Code Parameter Name
Setting Range Initial
Unit
Function
group 1
F27
[Torque Boost select]
0
0 ~ 1
0
F28
[Torque boost in forward direction]
-
0 ~ 15
2
%
F29
[Torque boost in reverse direction]
Set F27 to 0 {Manual torque boost}.
The values of [Torque boost in forward/reverse direction] are set separately in F28 and
F29.
CAUTION
If the boost value is set much higher than required, it may cause motor overheating or
inverter trips, due to over-energizing.
Auto torque boost
Group
Code Parameter Name
Setting Range
Initial
Unit
Function group 1
F27
[Torque Boost select]
1
0 ~ 1
0
Function group 2 H34
[No
load
motor
Current]
-
0.1 ~ 20
-
A
H41
[Auto tuning]
0
0 ~ 1
0
H42
[Stator resistance (Rs)] -
0 ~ 14
-
Ω
Before set Auto Torque Boost, H34 and H42 should be set correctly.
Select 1{Auto torque boost} in F27.
Inverter automatically calculates torque boost value using motor parameters and outputs
the corresponding voltage.
FX
Time
RX
Voltage
FX torque
boost
No torque boost
100%
RX torque
boost
Summary of Contents for Sinus M