10-8
10.4 3-Wire operation (Start – Stop via push buttons)
Group Display
Parameter Name
Setting
Range
Default Unit
I/O
group
I17
[Multi-function Input terminal
P1 select]
0
0 ~ 29
0
~
~
I24
[Multi-function Input
terminal P8 select]
17
7
Select a terminal from P1-P8 for use as 3-Wire operation.
If P8 is selected as stop, set I24 to 17 {3-Wire operation}.
Input signal is latched (saved) in 3-Wire operation.
Inverter operates by Push-buttons supplying the motor when Start push button is ON. The inverter
stops the motor when the Stop push button is OFF
The bandwidth of pulse (t) should not be less than 50msec.
FX
RX
Frequency
P8 (3-Wire)
t
P1
P2
P8
CM
FX : I17 = 0
RX : I18 = 1
3-Wire : I24 = 17
START RX
START FX
STOP