10-5
10.3 UP-DOWN
Up-down storage function
Group Display
Parameter Name
Setting
Range
Default Unit
Drive
group
Frq
[Frequency setting method] 8
0~8
0
I/O
group
I17
[Multi-function input
terminal P1 define]
0
0 ~ 29
0
I22
[Multi-function input
terminal P6 define]
25
5
I23
[Multi-function input
terminal P7 define]
15
6
I24
[Multi-function input
terminal P8 define]
16
7
Function
group 1
F63
[Up-down frequency Save
select]
-
0~1
0
F64
[Up-down frequency
storage]
-
0.00
Select 8 in Frq code of drive group
Select the terminal which is used as a up-down drive among multi-function inputs (P1~P8)
If you select P7 and P8 as an up-down drive terminal, select each 15 (frequency increase
command) and 16 (frequency decrease command) in the I23 and I24 of I/O group.
If you select P6 terminal as an up-down save initial terminal, select 25 (up-down save
initialization) as above.
Up/down Save function: If F63, ‘Save up/down frequency’, is set to 1, the frequency before
the inverter was stopped or decelerated is saved in F64.
While up-down save operates, the user can initialize the saved up-down frequency by setting multi-
function input terminal as a up-down frequency save initialization.
F63 Save up/down frequency select
0 Remove ‘save up/down frequency’
1
Set ‘save up/down frequency’
F64
Save up/down frequency
Up/down frequency saved
If ‘Up/Down Save Frequency Initialization’ signal is sent while the multi-function input ‘Up’ or ‘Down’
function is applied, this signal is ignored.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...