13-5
CMD: Capital letter
Character
ASCII-HEX
Command
‘R’
52h
Read
‘W’
57h
Write
‘X’
58h
Request for monitoring
‘Y’
59h
Action for monitoring
Data: ASCII-HEX
Ex) when data value is 3000: 3000 (dec) → ‘0’ ’B’ ’B’ ’8’h → 30h 42h 42h 38h
Error code: ASCII (20h ~ 7Fh)
Receive/Send buffer size: Receive= 39 bytes, Send=44 bytes
Monitor register buffer: 8 Word
SUM: to check the communication error
SUM= ASCII-HEX format of lower 8 bit of (Drive No. + CMD + DATA)
Ex) Command Message (Request) for reading one address from address “3000”
ENQ
Drive No
CMD
Address
Number of
address to read
SUM
EOT
05h
“01”
“R”
“3000”
“1”
“A7”
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
SUM = ‘0’ + ‘1’ + ’R’ + ‘3’ + ‘0’ + ‘0’ + ‘0’ + ‘1’
= 30h + 31h + 52h + 33h + 30h + 30h + 30h + 31h
= 1A7h (Control values such as ENQ/ACK/NAK are excluded.)
13.6.2 Detail communication protocol
1) Request for Read: Request for read successive ‘N’ numbers of WORD from address “XXXX”
ENQ
Drive
No
CMD
Address
Number of
address to read
SUM
EOT
05h
“01” ~
“1F”
“R”
“XXXX”
“1” ~ “8” = n
“XX”
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Total bytes = 12
The quotation marks (“ ”) mean a character.
1.1) Acknowledge Response:
ACK
Drive No
CMD
Data
SUM
EOT
06h
“01” ~ “1F”
“R”
“XXXX”
“XX”
04h
1 byte
2 bytes
1 byte
N * 4 bytes
2 byte
1 byte
Total bytes = 7 + n * 4 = Max 39
1.2) Negative Acknowledge Response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” ~ “1F”
“R”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes = 9
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...