9-7
9.2 Multi-Step Frequency setting
Group
Code Parameter Name
Setting Range
Initial
Unit
Drive group
0.0
[Frequency Command]
5.0
0 ~ 400
0.00
Hz
Frq
[Frequency Mode]
0
0 ~ 7
0
-
St1
[Multi-Step frequency 1] -
0 ~ 400
10.00
Hz
St2
[Multi-Step frequency 2] -
20.00
St3
[Multi-Step frequency 3] -
30.00
I/O group
I22
[Multi-function input
terminal P6 define]
5
0 ~ 29
5
-
I23
[Multi-function input
terminal P7 define]
6
6
-
I24
[Multi-function input
terminal P8 define]
7
7
-
I30
[Multi-Step frequency 4] -
0 ~ 400
30.00
Hz
I31
[Multi-Step frequency 5] -
25.00
I32
[Multi-Step frequency 6] -
20.00
I33
[Multi-Step frequency 7] -
15.00
Select a terminal to give Multi-step frequency command among P1-P8 terminals.
If terminals P6-P8 are selected, set I22-I24 to 5-7 to give Multi-step frequency command.
Multi-step frequency 0 is settable in
Frq
– [Frequency mode] and
0.00
– [Frequency
command].
Multi-step frequency 1-3 are set at St1-St3 in Drive group, while Step frequency 4-7 are
set at I30-I33 in I/O group.
Step
freq.
FX or RX P8 P7 P6
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
Freq.
P6
P7
P8
FX
RX
Step
0
Step
1
Step
2
Step
3
Step
4
Step
5
Step
6
Step
7
Step
0
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...