9.4 Accel/Decel time and pattern setting
Accel/Decel time setting based on Max frequency
Group
Code Parameter Name
Setting Range
Initial
Unit
Drive group
ACC [Accel time]
-
0 ~ 6000
5.0
Sec
dEC
[Decel time]
-
0 ~ 6000
10.0
Sec
Function group1
F21
[Max Frequency]
-
40 ~ 400
50.00
Hz
Function group2
H70
[Frequency
Reference for
Accel/Decel]
0
0 ~ 1
0
H71
[Accel/Decel time
scale]
-
0 ~ 2
1
Set the desired Accel/Decel time at ACC/dEC in Drive group.
If H70 is set to 0 {Max frequency}, Accel/Decel time is the time that takes to reach the max
freq from 0 Hz.
Desired Accel/Decel time unit is settable at the H71.
Accel/Decel time is set based on
F21
– [Max frequency]. For instance, if
F21
is set to 60Hz,
Accel/Decel time 5 sec, and run frequency 30Hz, time to reach 30Hz would be 2.5 sec.
Run
command
Run Freq.
30Hz
Accel time
Decel time
Max. freq.
60Hz