10-16
10.7.1 PID reference
LED
display
Parameter
name
Setting
Range
Description
Factory
defaults
Adj.
during
Run
H49
PID control
select
0~1
Selects whether using PID control or not
0
X
- User can select the PID control mode in H49. For PID control, the setting value should be set to
“1”.
- Then REF and FBK category show.
LED
display
Parameter
name
Setting
Range Description
Factory
defaults
Adj.
during
Run
H57
[PID
reference
source
select]
0~4
Selects the PID reference source.
The reference is indicated in “rEF” of
Drive group.
0
X
0 Keypad digital setting 1
1 Keypad digital setting 2
2 V1 terminal setting 2: 0~10V
3 I terminal setting: 0~20mA
4 Setting as RS-485 communication
- One among Multistep frequency values 1-3 and 4-7 can also be used as a PID Reference.
Multistep frequency values 1-3 are set in St1-St3 in the Drive Group; Multistep frequency values 4-7
are set in I30-I33 in the I/O Group.