11-10
2: FDT-3
Activated when run frequency meets the following condition.
Active condition: Absolute value (FDT level - run frequency)
≤
FDT Bandwidth/2
Group
Display
Parameter Name
Setting
Range Default Unit
I/O group
I52
[Detected Frequency
level]
-
0 ~ 400
30.00
Hz
I53
[Detected Frequency
Bandwidth]
-
10.00
Cannot be set above Max frequency (F21).
When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively
3: FDT-4
Activated when run frequency meets the following condition.
Active condition:
Accel time: Run Frequency
≥
FDT Level
Decel time: Run Frequency > (FDT Level – FDT Bandwidth/2)
Group
Display
Parameter Name
Setting
Range Default Unit
I/O group
I52
[Detected Frequency
level]
-
0 ~ 400
30.00
Hz
I53
[Detected Frequency
Bandwidth]
-
10.00
Cannot be set above Max frequency (F21).
When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively
Freq.
MO
Run
command
25Hz
30Hz
35Hz
Freq.
MO
Run
command
25Hz
30Hz