10-49
LED
display Parameter name
Setting
range
Description
Factory
defaults
Adj.
during
Run
I88
Fire Mode
Frequency
0.00~400.00Hz Command frequency
when in Fire mode
50.00 Hz
O
I96
Fire Mode
Evidence
0 ~ 1
0 : No trip occurred during
Fire mode
-
Display
only
1 : Trip occurred during
Fire mode
Caution:
Once the Fire mode is activated, the drive cannot return to its previous operating
conditions. To restore normal operating conditions, turn off and on the inverter in order to reboot
its control board.
Caution:
Once the Sinus M enters the Fire mode, no alarm previously tripped may be reset.
To deactivate the Fire mode, turn off and on the inverter AND disable the Fire Mode input.
Failure to do so will prevent the alarms tripped from being displayed when the Sinus M is
normally operating.
When in Fire-mode, the target frequency should be 50Hz and the ACC/DEC time should be set
to 10sec. If the user attempts to change these values when the inverter is running, the output
frequency is left unchanged (50Hz), whereas the new values for ACC/DEC become effective
only after disabling the Fire mode.