13-4
13.5 Communication protocol (MODBUS-RTU)
Use Modbus-RTU protocol (Open protocol).
Computer or other hosts can be Master and inverters Slaves. Inverter responds to Read/Write
command from Master.
Supported function code
Function code
Description
0x03
Read Hold Register
0x04
Read Input Register
0x06
Preset Single Register
0x10
Preset Multiple Register
Exception code
Function code
Description
0x01
ILLEGAL FUNCTION
0x02
ILLEGAL DATA ADDRESS
0x03
ILLEGAL DATA VALUE
0x06
SLAVE DEVICE BUSY
User define
0x14
1.Write Disable (Address 0x0003 value is 0).
2.Read Only or Not Program during Running.
13.6 Communication protocol (ES BUS)
13.6.1 Basic format
Command message (Request):
ENQ
Drive No.
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n bytes
2 bytes
1 byte
Normal response (Acknowledge Response):
ACK
Drive No.
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n * 4 bytes
2 bytes
1 byte
Negative response (Negative Acknowledge Response):
NAK
Drive No.
CMD
Error code
SUM
EOT
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Description:
Request starts with “ENQ” and ends with “EOT”.
Acknowledge Response starts with “ACK” and ends with “EOT”.
Negative Acknowledge Response starts with ”NAK” and ends with “EOT”.
“Drive Number” is the number of drives and indicated in 2 bytes ASCII-HEX.
(ASCII-HEX: Hexadecimal consists of ‘0’ ~ ‘9’, ‘A’ ~ ‘F)
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...