10-20
10.7.3 PID Limit
LED
display Parameter name
Setting
range
Description
Factory
defaults
Adj.
during
Run
H55
PID output
frequency low
limit
0 to 400Hz
This parameter limits the low
amount of the output
frequency through the PID
control.
50.00Hz
O
H56
PID output
frequency high
limit
0 to 400Hz
This parameter limits the high
amount of the output
frequency through the PID
control.
0.5Hz
O
-
PID low limit is the additional function code of Sinus M. H55 and H56 are related to each low
limit and high limit. When the drive runs, the output frequency should be reached to low limit
even if the feedback is higher than the reference. So, except during acceleration time from 0Hz
to low limit, the output frequency is between low limit and high limit at any time.
10.7.4 Inverse PID
LED
display Parameter name
Setting
range
Description
Factory
defaults
Adj.
during
Run
H59
Inverse PID
0 ~ 1
0
Normal
0
X
1
Inverse
-
To stabilize the system (negative feedback system), the sensor output is high when the real
physical value is high. Sometimes, however, the sensor output is inverse, or the system needs
higher output when the signal is low. In that case, the inverse PID is used.
-
For this functionality, H59 code is used. PID output is increased when PID reference is higher
than feedback setting value “0”. PID output is decreased when PID reference is higher than
feedback setting value “1”.
-
When H59 is set to 1, the FBK display is the same. That is to say, the feedback is the same, but
the error is inverse.
-
This functionality affects Sleep and Wake Up operation. (Refer to Sleep & Wake up functionality
below).
10.7.5 Sleep & Wake up functionality
LED
display
Parameter
name
Setting
range
Description
Factory
defaults
Adj.
during
Run
H61
Sleep delay
time
0 ~ 999
(sec)
Delay time in Sleep mode
60 sec X
H62
Sleep
frequency
0 ~ 400Hz
Frequency in Sleep mode
0.0Hz
O
H63
Wake-up level
0 ~ 50[%]
Wake Up level
2[%]
O
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...