11-7
11.4 Analog Output
Group
Display
Parameter Name
Setting
Range
Default Unit
I/O group
I50
[Analog output item select] -
0 ~ 3
0
I51
[Analog output level
adjustment]
-
10 ~ 200 100
%
Output item and the level from the AM terminal are selectable and adjustable.
I50: The selected item will be output on the Analog output terminal (AM).
I50
Analog output
item select
Item corresponding to 10V
200V
400V
0
Output frequency.
Max Frequency (F21)
1
Output current
150% of Inverter rated
current
2
Output voltage
282Vac
564Vac
3
Inverter DC link
voltage
400Vdc
800Vdc
I51: If you want to use Analog output value as an input signal for instruments, the value can be
adjustable according to instruments specifications.
AM
CM
0 ~ 10Vdc