6-2
Frequency Setting via potentiometer & operating via terminals
1
-. Apply AC input power to the inverter.
2
-. When 0.00 appears Press the Up (
) key four times.
3
-. Frq is displayed. Frequency setting mode is selectable.
-. Press the Ent (
) key once.
4
-. Present setting method is set to 0 (frequency setting via keypad).
-. Press the Up (
) key three times.
5
-. After 3 (Frequency setting via potentiometer) is set, press the Ent (
) key once.
6
-. Frq is redisplayed after 3 stops blinking.
-. Turn the potentiometer to set to 10.00 Hz in either Max or Min direction.
7
-. Turn on the switch between P1 (FX) and CM (See Wiring below).
-. RUN lamp begins to blink with FWD lamp lit and the accelerating frequency is
displayed on the LED.
-. When run frequency 10Hz is reached, the value is displayed as shown left.
-. Turn off the switch between P1 (FX) and CM terminals.
8
-. RUN lamp begins to blink and decelerating frequency is displayed on the LED.
-. When run frequency is reached to 0Hz, Run and FWD lamp turn off and
10.00
is displayed.
3P AC
input
R
S
G
P1(FX)
CM
U
V
W
Motor
T
VR
V1
CM
Freq.
P1(FX)-CM
ON
OFF
10 Hz
Wiring
Operating pattern
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...