10-44
Inverter
Remote
keypad
Parameter Write(H92)
Parameter Read(H91)
10.24 Parameter read/write
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 2
H91
[Parameter read]
1
0 ~ 1
0
H92
[Parameter write]
1
0 ~ 1
0
Used to read/write Inverter Parameters using remote keypad.
Caution:
Take caution when Parameter write (H92) is executed. By doing this, operation inverter
parameters are cleared and the parameters of remote the remote keypad are copied into the
inverter.
Parameter read
Step
Note
Keypad display
1
Move to H91 code.
H91
2
Press Enter (
) key once.
0
3
Press Up (
) key once.
rd
4
Press Enter (
) key twice.
rd
5
H91 is displayed when Parameter read is finished.
H91
Parameter write
Step
Note
Keypad display
1
Move to H92 code.
H92
2
Press Enter (
) key once.
0
3
Press Up (
) key once.
Wr
4
Press Enter (
) key twice.
Wr
5
H91 is displayed when Parameter read is finished.
H92
During parameter reading (H91), the display of the remote keypad shows “rd”(Read) and
“vr”(Verify), whereas during parameter writing (H92) the display only shows “wr”(Write).
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...