10-22
10.7.6 Open Loop1 (Addtional)
LED
display Parameter
Min/Max
range
Description
Factory
defaults
Adj.
During
run
I17
Multi-function
input
terminal P1 define
0 ~ 29
0
Forward run command (FX)
0
O
1
Reverse run command (RX)
I18
Multi-function
input
terminal P2 define
2
Emergency Stop Trip
1
O
3
Reset when a fault occurs
I19
Multi-function
input
terminal P3 define
4
Jog operation command
2
O
5
Multi-step freq- Low
I20
Multi-function
input
terminal P4 define
6
Multi-step freq- Middle
3
O
7
Multi-step freq- High
I21
Multi-function
input
terminal P5 define
8
Multi Accel/Decel-Low
4
O
9
Multi Accel/Decel-Middle
I22
Multi-function
input
terminal P6 define
10 Multi Accel/Decel-High
5
O
11 DC brake during hold
I23
Multi-function
input
terminal P7 define
12 2nd motor select
6
O
13 -Reserved-
I24
Multi-function
input
terminal P8 define
14 -Reserved-
7
O
15 Up-
down
Frequency
increase command
16
Frequency
decrease
command
17 3-wire operation
18 External trip: A contact (EtA)
19 External trip: B contact (EtB)
20 Self-diagnostic function
21 Change PID operation to
normal operation
22 2nd source select
23 Analog hold
24 Accel/Decel hold
25 Up/Down Save
Freq.Initialization
26 JOG-FX
27 JOG-RX
28 Open Loop1
29 Fire Mode
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...