7-4
7.2 Function group 1
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
F0
[Jump code]
0 ~ 64
Sets the parameter code number to
jump.
1
O
F1
[Forward/
Reverse run
disable]
0 ~ 2
0
Fwd and rev run enable
0
X
1
Forward run disable
2
Reverse run disable
F2
[Accel pattern] 0 ~ 1
0
Linear
0
X
F3
[Decel pattern]
1
S-curve
F4
[Stop mode
select]
0 ~ 3
0
Decelerate to stop
0
X
1
DC brake to stop
2
Free run to stop
3
Power braking stop
F8
1)
[DC Brake
start
frequency]
0.1 ~ 60
[Hz]
This parameter sets DC brake start
frequency.
It cannot be set below F23 - [Start
frequency].
5.00
X
F9
1)
[DC Brake
wait time]
0 ~ 60
[sec]
When DC brake frequency is reached,
the inverter holds the output for the
setting time before starting DC brake.
0.1
X
F10
1)
[DC Brake
voltage]
0 ~ 200
[%]
This parameter sets the amount of DC
voltage applied to a motor.
It is set in percent of H33 – [Motor rated
current].
50
X
F11
1)
[DC Brake
time]
0 ~ 60
[sec]
This parameter sets the time taken to
apply DC current to a motor while
motor is at a stop.
1.0
X
F12
[DC Brake
start voltage]
0 ~ 200
[%]
This parameter sets the amount of DC
voltage before a motor starts to run.
It is set in percent of H33 – [Motor rated
current].
50
X
F13
[DC Brake
start time]
0 ~ 60
[sec]
DC voltage is applied to the motor for
DC Brake start time before motor
accelerates.
0
X
F14
[Time for
magnetizing a
motor]
0 ~ 60
[sec]
This parameter applies the current to a
motor for the set time before motor
accelerates during Sensorless vector
control.
1.0
X
F20
[Jog
frequency]
0 ~ 400
[Hz]
This parameter sets the frequency for
Jog operation.
It cannot be set above F21 – [Max
frequency].
10.00
O
1)
: Displayed only when F4 is set to 1 (DC brake to stop).
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...