9-4
Frequency setting via 0 ~ 10 [V] input or Terminal Potentiometer
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive group 0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
3
0 ~ 8
0
I/O group
I6
[Filter time constant for V1
input]
10
0 ~ 9999 10
I7
[V1 input Min voltage]
-
0 ~ 10
0
V
I8
[Frequency corresponding
to I7]
-
0 ~ 400
0.00
Hz
I9
[V1 input max voltage]
-
0 ~ 10
10
V
I10
[Frequency corresponding
to I9]
-
0 ~ 400
50.00
Hz
Select 3 in Frq code of Drive group.
0-10V can be directly applied from an external controller or a potentiometer connected on
terminals VR, V1 and CM.
Wire the terminals as shown below and refer to page 9-3 for I6 ~ I10.
Frequency setting via 0 ~ 20 [mA] input
Group Code Parameter Name
Setting Range
Initial
Unit
Drive
group
0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
4
0 ~ 8
0
I/O
group
I11
[Filter time constant for I input]
10
0 ~ 9999 10
I12
[I input minimum current]
-
0 ~ 20
4
mA
I13
[Frequency corresponding to I12] -
0 ~ 400
0.00
Hz
I14
[I input max current]
-
0 ~ 20
20
mA
I15
[Frequency corresponding to I14] -
0 ~ 400
50.00
Hz
Select 4 in Frq code of Drive group.
Frequency is set via 0~20mA input between I and CM terminal.
VR
V1
CM
Wiring of potentiometer
V1
CM
0 ~ 10V input via external controller
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...