12-4
For example, set F59 to 3 to make stall prevention active during Acceleration and constant run.
When stall prevention is executed during acceleration or deceleration, Accel/Decel time may take
longer than the user-setting time.
When stall prevention is activated during constant run, t1, t2 are executed in accordance with the value
set in ACC - [Accel time] and dEC - [Decel time].
Current
Freq.
During
acceleration
During
constant run
F60
t1
t2
Multi-functi
on output
or relay
DC
voltage
Freq.
During
deceleration
Multi-function
output or relay