9-10
Rotating direction selection via –10 ~ +10[V] input of V1 terminal
Group
Code Parameter Name
Setting
Range
Initial
Unit
Drive group
frq
[Frequency setting]
2
0 ~ 7
0
drv
[Drive mode]
-
0 ~ 3
1
Set
frq
to 2.
Inverter is operating as the table below regardless of Drive mode setting.
FWD RUN Command
REV RUN Command
0 ~ +10 [V]
FWD RUN
REV RUN
–10 ~ 0 [V]
REV RUN
FWD RUN
Motor runs in Forward direction when input voltage to V1-CM is 0~10[V] and FWD RUN command is
active. When input voltage polarity is reversed to –10~0[V] during FWD RUN, motor decelerates to stop
and runs in reverse direction.
When input voltage to V1-CM is 0~10[V] and REV RUN command is active, motor runs in Reverse
direction and if –10~0[V] is entered, the motor rotating direction is reverse.
FX/RX Run Disable
Group
Code Parameter Name
Setting
Range Initial Unit
Drive group
drC
[Direction of motor
rotation select]
-
F, r
F
Function group 1
F1
[Forward/Reverse run
disable]
-
0 ~ 2
0
Select the direction of motor rotation.
0: Forward and Reverse run enable
1: Forward run disable
2: Reverse run disable