7-14
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
H52
2)
[Integral
time for PID
controller
(I gain)]
0.1~32.0
[sec]
1.0
O
H53
2)
[Differential
time for PID
controller (D
gain)]
0 ~ 30.0
[sec]
0.0
O
H54
2)
[PID control
mode
select]]
0 ~ 1
Selects PID control mode
0
X
0
Normal PID control
1
Process PID control
H55
2)
[PID output
frequency
high limit]
0.1~400[Hz] This parameter limits the amount of the
output frequency through the PID control.
The value is settable within the range of
F21 – [Max frequency] and F23 – [Start
frequency].
50.00
O
H56
2)
[PID output
frequency
low limit]
0.1~400[Hz]
0.50
O
H57
[PID
reference
source
select]
0~4
Selects PID reference source.
Reference is indicated in “rEF” of Drive
group.
0
X
0
Keypad digital setting 1
1
Keypad digital setting 2
2
V1 terminal setting 2: 0~10V
3
I terminal setting: 0~20mA
4
Setting as RS-485 communication
H59
Inverse PID 0 ~ 1
0
Normal
0
X
1
Inverse
H60
[Self-
diagnostic
select]
0 ~ 3
0
Self-diagnostic disabled
0
X
1
IGBT fault/Ground fault
2
Output phase short & open/ Ground
fault
3
Ground fault
1)
: Set H40 to 3 (Sensorless vector control) to display this parameter.
2)
: Set H40 to 2 (PID control) to display this parameter.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...