7-7
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
F53
2)
[Motor cooling
method]
0 ~ 1
0
Standard motor having cooling
fan directly connected to the
shaft
0
0
1
A motor using a separate motor
to power a cooling fan.
F54
[Overload
warning level]
30 ~ 150
[%]
This parameter sets the amount of
current to issue an alarm signal to the
relay or multi-function output terminal
(see I54, I55).
The set value is a percentage of H33-
[Motor rated current].
150
0
F55
[Overload
warning time]
0 ~ 30
[Sec]
Delay time of the current level set in
F54- [Overload warning level]
10
0
F56
[Overload trip
select]
0 ~ 1
This parameter turns off the inverter
output when motor is overloaded.
1
0
F57
[Overload trip
level]
30 ~ 200
[%]
This parameter sets the amount of
overload current.
The value is the percentage of H33-
[Motor rated current].
180
0
F58
[Overload trip
time]
0 ~ 60
[Sec]
This parameter turns off the inverter
when the current greater than F57-
[Overload trip level] flows to the motor
for F58- [Overload trip time].
60
0
2)
: Set F50 to 1 to display this parameter.
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...