10-10
10.6 Slip compensation
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 2
H30
[Motor type select]
-
0.2 ~ 7.5
7.5
H31
[Number of motor poles] -
2 ~ 12
4
H32
[Rated slip frequency]
-
0 ~ 10
2.33
Hz
H33
[Motor rated current]
-
0.5 ~ 50
26.3
A
H34
[Motor No Load Current] -
0.1 ~ 20
11.0
A
H36
[Motor efficiency]
-
50 ~ 100
87
%
H37
[Load inertia rate]
-
0 ~ 2
0
H40
[Control mode select]
1
0 ~ 3
0
Set H40 – [Control mode select] to 1 {Slip compensation}.
This function allows the motor to run in constant speed by compensating slip in an
induction motor.
H30: Set the motor type connected to the inverter output side.
H30
[Motor type select] 0.2
0.2kW
~
5.5
5.5kW
7.5
7.5kW
H31: Enter the pole number as shown on the Motor nameplate.
H32: Enter the slip frequency in accordance with the following formula and motor nameplate.
×
−
=
120
P
rpm
f
f
r
s
Where,
s
f
= Rated slip frequency
r
f
= Rated frequency
rpm
= Motor rated RPM
P
= Motor pole number
Ex) Rated freq.: 60Hz, Rated RPM: 1740rpm, Poles: 4,
Hz
f
s
2
120
4
1740
60
=
×
−
=
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...