10-7
When F65 is 1: It is increased as much as the step frequency set as F66 at the rising edge of multi-
function input set as UP and when up-down is defined, it saves frequency at the falling edge. It is
decreased as much as the step frequency set as F66 at the falling edge of rising edge of multi-function
input set as DOWN and when up-down is defined, it saves frequency as the falling edge. In this case,
while multi-function input set as UP or DOWN is defined, if a stop command is given, the previous falling
edge value is saved and if multi-function input is not defined, the present frequency is not saved. The
accel/decel time is the same as when set as “0”.
When F65 is 2: It is increased as much as step frequency set as F66 at the rising edge of multi-function
input set as UP and if it is activated for 3 seconds, it operates as it was set as “0”. It is decreased as
much as the step frequency set as F66 at the rising edge of multi-function input set as DOWN. If it is
activated for 3 seconds, it operates as it was set as “0” and the accel/decel time is the same as when set
as “0”.
CAUTION
Because of UP or DOWN, when the input is entered again before it is increased as much
as 1 step frequency, the input is ignored and the saved frequency is also the frequency
of the inactive moment.
Fx or Rx
Up
Down
Output
Frequency
Up/Dn Clr
Over 3sec
Memorized
Frequency
Fx or Rx
Up
Down
Up/Dn Clr
3sec
Output
Frequency
Memorized
Frequency
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...