12.4 Input/Output phase loss protection
Group
Code Parameter
Set
Range
Initial
Unit
Function
group 2
H19
[Input/Output
phase
loss
protection select]
1
0 ~ 3
0
Set H19 value to 1
Output phase loss: Inverter output is shut off at the event of one or more output phase
loss among U, V and W.
Set H19 value to 2
Input phase loss: Inverter output is shut off at the event of one or more input phase loss
among R, S and T. If there is no input phase loss, output is shut off when it is time to replace
DC link capacitor.
Set H19 value to 3
Input/output phase loss: Inverter output is shut off at the event of one or more input or
output phases loss among R, S and T or U, V and W If there is no input or output phase loss,
output is shut off when it is time to replace DC link capacitor.
Caution:
Set H33- [Motor rated current] correctly. If the actual motor rated current and the value of H33
are different, output phase loss protection function could not be activated.
H19
[Input/Output
phase loss
protection
select]
Both bars down
Not used
Right hand (low bit) UP
Output phase loss protection
Left hand (high bit) UP
Input phase loss protection
Both bars UP
Input/output phase loss protection
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...