3.2 Power terminal block
0.4 ~ 1.5kW
2.2 ~ 4.0kW
5.5 ~ 7.5kW
11.0 ~ 22.0kW
B1
W
B2 U V
R S T
R,S,T
Wire Size
U, V, W
Wire Size
Ground
Wire
Screw Size
Terminal
Torque
mm
2
AWG mm
2
AWG mm
2
AWG
Terminal
Screw Size
Screw Torque
(kgf·cm/lb·in)
SINUS M 0001 2S/T 2.5
14
2.5
14
4
12
M3.5
10/8.7
SINUS M 0002 2S/T 2.5
14
2.5
14
4
12
M3.5
10/8.7
SINUS M 0003 2S/T 2.5
14
2.5
14
4
12
M3.5
10/8.7
SINUS M 0005 2S/T 2.5
14
2.5
14
4
12
M4
15/13
SINUS M 0007 2S/T
4
12
4
12
4
12
M4
15/13
SINUS M 0011 2S/T
6
10
6
10
6
10
M5
32/28
SINUS M 0014 2S/T
10
8
10
8
6
10
M5
32/28
SINUS M 0017 2S/T
16
6
16
6
16
6
M6
30.7/26.6
SINUS M 0020 2S/T
20
4
20
4
16
6
M6
30.7/26.6
SINUS M 0025 2S/T
35
2
35
2
20
4
M8
30.6/26.5
SINUS M 0030 2S/T
35
2
35
2
20
4
M8
30.6/26.5
SINUS M 0001 4T
2.5
14
2.5
14
2.5
14
M3.5
10/8.7
SINUS M 0002 4T
2.5
14
2.5
14
2.5
14
M3.5
10/8.7
SINUS M 0003 4T
2.5
14
2.5
14
2.5
14
M4
15/13
SINUS M 0005 4T
2.5
14
2.5
14
2.5
14
M4
15/13
SINUS M 0007 4T
2.5
14
2.5
14
2.5
14
M4
15/13
SINUS M 0011 4T
4
12
2.5
14
4
12
M5
32/28
SINUS M 0014 4T
4
12
4
12
4
12
M5
32/28
SINUS M 0017 4T
6
10
6
10
10
8
M5
30.7/26.6
SINUS M 0020 4T
16
6
10
8
10
8
M5
30.7/26.6
SINUS M 0025 4T
16
6
10
8
16
6
M6
30.6/26.5
SINUS M 0030 4T
20
4
16
6
16
6
M6
30.6/26.5
* Strip the sheaths of the wire insulation for 7mm when a ring terminal is not used for power
connection.
*For Sinus M 0025 and Sinus M 0030, UL-approved Ring or Fork Terminals must be used.
7.0mm
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...