12-3
Overload trip
Group
Code
Parameter
Set
Range
Initial
Unit
Function
group 1
F56
[Overload trip select]
1
0 ~ 1
1
F57
[Overload trip level]
-
30 ~ 200
180
%
F58
[Overload trip time]
-
0 ~ 60
60
sec
Set F56 to 1.
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when excessive current flows to the motor for F58 – [Overload trip
time].
12.3 Stall prevention
Group
Code Parameter
Set
Range
Initial
Unit
Function
group 1
F59
[Stall prevention select]
-
0 ~ 7
0
F60
[Stall prevention level]
-
30 ~ 200
150
%
I/O group
I54
[Multi-function output terminal
select]
7
0 ~18
12
I55
[Multi-function relay select]
7
17
During acceleration: Motor acceleration ramp is stopped when current exceeds the value set in
F60.
During constant run: Motor decelerates when current exceeds the value set in F60.
During deceleration: Motor deceleration ramp is stopped when inverter DC link voltage rises
above a certain voltage level.
F60: The value is set as the percent of motor rated current (H33).
I54, I55: Inverter outputs signals through multi-function output terminal (MO) or relay output
(3ABC) or external sequence when stall prevention function is activated. Motor stall status can be
monitored setting F59 different from (000).
F59: Stall prevention can be set as the table below.
F59
Stall prevention
Setting
During
Deceleration
During
constant
speed
During
Acceleration
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
Summary of Contents for Sinus M
Page 10: ......
Page 15: ...1 5 Notes...
Page 16: ......
Page 50: ...6 4 Notes...
Page 78: ...8 4 Notes...
Page 114: ...10 14 Normal PID block diagram H54 0...
Page 115: ...10 15 Process PID block diagram H54 1...
Page 150: ...10 50 Notes...
Page 174: ......
Page 192: ...13 18 Notes...
Page 204: ......
Page 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...