2-1
CHAPTER 2 - INSTALLATION
2.1 Installation precautions
CAUTION
Handle the inverter with care to prevent damage to the plastic components. Do not hold the
inverter by the front cover. It may fall off.
Install the inverter in a place where it is immune to vibration (5.9 m/s
2
or lower).
Install in a location where temperature is within the permissible range (–10~50
°
C).
<Ambient Temp Checking Location>
The inverter will be very hot during operation. Install it on a non-combustible surface.
Mount the inverter on a flat, vertical and level surface. Inverter orientation must be vertical
(top up) for proper heat dissipation. Also leave sufficient clearances around the inverter.
Protect from moisture and direct sunlight.
Do not install the inverter in any environment where it is exposed to waterdrops, oil mist,
dust, etc. Install the inverter in a clean place or inside a “totally enclosed” panel any
suspended matter is not entered.
5cm
Min
10cm Min
5cm
Min
10cm Min
Ventilating fan
Cooling air
Leave space enough to
allow cooled air flowing
easily between wiring
duct and the unit